Certified in accordance with MID 2014/32/EU MI004.
Why Choose the ATLAS Solenoid Valve Control Solution?
The ATLAS solenoid valve control solution uses the installation’s own water pressure to operate a diaphragm main valve. Filling or draining the control chamber produces valve movement. Manual three-way control or an optional electrically operated solenoid pilot can be selected for field operating requirements.
Normally open and normally closed solenoid options support the required control behaviour. A one-way flow restrictor supplied within the order scope can adjust closing speed, helping commissioning account for hydraulic conditions. It is not a guarantee of surge-free operation in every situation.
The technical table lists EN-GJS-400-15 main valve material, DN50–DN400 sizes and PN10/PN16 options for different water lines. The stated 2–40 °C range and selected pilot-circuit characteristics are checked against the application’s pressure, temperature and electrical control requirements.
Key benefits
- Diaphragm main valve control using system pressure.
- Manual control or optional solenoid pilot.
- Project-specific size, pressure rating and closing-speed selection.
Working Principle | ||
|---|---|---|
Working Principle | Control Type | Manual 3-way valve or Optional Electric Solenoid Valve |
| Working Mechanism | Filling and emptying of the diaphragm with the system's own pressure | |
| Solenoid Modes | Normally Open (NO) or Normally Closed (NC) (Positive/Negative control) | |
| Speed Adjustment | Closing speed can be adjusted with a one-way flow restrictor (During ordering) | |
Structural Features | ||
Structural Features | Basic Parts | Body, Cover and Diaphragm |
| Diaphragm Design | "Springless" design (Distributes pressure evenly, prevents deformation, long-lasting) | |
| Closing Characteristic | Gradual closing (Prevents water hammer) | |
| Maintenance | Contains minimum moving parts, practically maintenance-free | |
| Performance | Precise regulation at low flow rates, full opening at low pressure (Low head loss) | |
Technical Data | ||
Technical Data | Diameter Range | DN50 - DN400 |
| Operating Pressure | PN10 - PN16 | |
| Temperature Range | Between 2°C and 40°C | |
| Main Valve Material | EN-GJS-400-15 | |
| Standards | DIN / ANSI / BS compliant | |
Connections and Indicators | ||
Connections and Indicators | Flanges | DIN 1092-2 (Can be changed upon request) |
| Pressure Indicator | EN 837-1; Accuracy class 1.6 | |