Ultrasonic Heat Meters

ATLAS UKM ultrasonic heat meters measure energy consumption in heating and cooling systems, with M-Bus, pulse and LoRa/LoRaWAN communication options.
ATLAS UKM20 DN20 ultrasonik ısı sayacı, pirinç gövde ve M26 ürün etiketi
Certified in accordance with MID 2014/32/EU MI004.

LoRaM-BusM-BusWIRELESSRS-485

Why Choose ATLAS UKM Ultrasonic Heat Meters?

ATLAS UKM ultrasonic heat meters are designed for accurate measurement and monitoring of energy consumption in heating and cooling installations. Ultrasonic flow measurement operates without moving mechanical measuring parts. Certification under MID 2014/32/EU MI-004 provides metrological assurance for energy measurement.

M-Bus and other communication options allow integration with central meter reading, building automation and remote monitoring systems. Models suited to different installation requirements help make energy consumption transparent in residential and commercial buildings.

Key benefits

  • MID MI-004 certified measurement.
  • Ultrasonic flow measurement technology.
  • Remote reading and communication options.
  • Integration with building automation systems.
ATLAS UKM20 DN20 · LCD display, brass body and Pt1000 temperature probe
Digitally edited UKM20 / DN20 product image. Refer to current official product documents for technical labels and conformity markings.

UKM series ultrasonic heat meters

ATLAS UKM ultrasonic heat meters measure energy in heating and cooling circuits. Select the body material, installation orientation and connection dimensions for the required model. M-Bus, pulse and LoRa/LoRaWAN communication options must match the ordered hardware and reading infrastructure. Models with the appropriate interface can connect to remote reading systems through ATLAS CNV or a LoRaWAN Gateway.

UKM product details · UKM20

ATLAS UKM20 DN20 · LCD display, brass body and Pt1000 temperature probe

LCD display, brass body and Pt1000 temperature probe · DN20 · PN16 · IP65 · 5–90 °C · 1″ · 130 mm

The sample label in the product image shows qᵢ 0.070 m³/h. For selection use qᵢ 0.030 m³/h from the technical table and confirm the ordered configuration.

How the ultrasonic heat meter works

The meter measures flow ultrasonically and records the supply and return temperatures. It uses the temperature difference and flow to calculate thermal power and integrates that power over time to determine energy consumption.

ATLAS UKM20 DN20 · LCD

UKM series flow rates and connection dimensions

The ATLAS UKM range covers DN15–DN200. DN125, DN150 and DN200 catalogue values support preliminary hydraulic selection. Confirm the temperature difference, conformity scope and connection revision for the selected model. DN250 and DN300 are catalogue references; confirm current availability.

ModelDNConnectionqₚ (m³/h)qᵢ (m³/h)qₛ (m³/h)L (mm)H (mm)W (mm)Weight (g)
UKM15153/4″ threaded1.500.0153.001109483950
UKM20201″ threaded2.500.035.001309483950
UKM25251¼″ threaded3.500.067.0016010083–
UKM32321½″ threaded6.000.0612.00180100831100
UKM40402″ threaded10.000.1020.00200120831250
UKM5050Flanged15.000.1530.00200165165–
UKM6565Flanged25.000.2550.00200185185–
UKM8080Flanged40.000.4080.00220200200–
UKM100100Flanged60.000.60120.00250220220–
UKM125125Flanged100.001.00200.00250250250–
UKM150150Flanged150.001.50300.00300285285–
UKM200200Flanged250.002.50500.00350340340–
UKM250250Flanged400.004.00800.00450405405–
UKM300300Flanged560.005.601120.00500460460–

Minimum flow rate and model documentation

The minimum flow rates shown for UKM15–UKM100 correspond to the models covered by type examination. Check flow rates and installation dimensions for UKM125–UKM300 against the technical data sheet for the model being ordered.

Selecting an ultrasonic heat meter

Pipe size alone is not enough to select a heat meter. Consider the minimum and nominal flow rates, installation length, connection type and communication requirements together.

  • Flow range: Compare each model’s minimum, nominal and maximum flow rates in the table above.
  • Installation: Match the DN, connection size and body length to the system design.
  • Operating conditions: Check temperature, pressure and protection ratings against the selected model’s technical documentation.

What is the difference between UKM15 and UKM20?

The table specifies a nominal flow rate of 1.50 m³/h and an installation length of 110 mm for UKM15, compared with 2.50 m³/h and 130 mm for UKM20. Select the model according to the system’s flow requirements and connection dimensions.

How do mechanical and ultrasonic heat meters compare?

Ultrasonic models measure flow using an ultrasonic principle without moving parts in the flow sensor. Mechanical heat meters use a mechanical flow sensor. Compare each model’s flow range, installation conditions and reading infrastructure.

Remote reading options

Assess M-Bus, pulse and LoRa/LoRaWAN options against your existing automation infrastructure. Explore M-Bus converters and the LoRaWAN Gateway. Confirm communication hardware and compatibility when ordering.

Request a project quotation

Provide the model or DN, design flow rate, installation length, quantity and preferred communication interface.

Request an ultrasonic heat meter quotation

Compare certified ATLAS UKM models

Explore model-specific MID MI-004 technical data, accuracy class 2, IP65 and qp/qi/qs values before choosing a heat meter.

UKM20 DN20 technical data · UKM25 DN25 technical data

Flow ratio and example thermal power

For water, P (kW) ≈ 1.163 × Q (m³/h) × ΔT (K). At the stated flow and ΔT = 20 K, the approximate powers are shown below. These values describe example operating points.

P (kW) ≈ 1.163 × Q (m³/h) × ΔT (K)

UKM20 · qₚ/qᵢ ≈ 83:1 · 2.50 m³/h · 58.2 kW
UKM25 · qₚ/qᵢ ≈ 58:1 · 3.50 m³/h · 81.4 kW

Selection and remote reading

Check minimum and permanent flow, connection size, installation length, operating temperature, pressure and permitted mounting position. Match M-Bus, pulse or LoRa/LoRaWAN to the ordered hardware. Specify measurement, logging and transmission intervals separately, including how data is recovered after an interruption.

Frequently asked questions

Can I select the meter by pipe diameter alone?

Check design flow, installation length, pressure, temperatures and the required interface alongside DN.

How is energy calculated?

The calculator integrates thermal power derived from flow and the difference between supply and return temperatures.

Can it be read remotely?

Yes, with a compatible interface in the ordered configuration and matching reading infrastructure.

What information is needed for a quotation?

Provide model or DN, design flow, installation length, quantity and preferred interface.

General Structure and Design
General Structure and Design
Product Description

Ultrasonic heat meter used in heating and cooling systems

Principle of Measurement

Ultrasonic flow measurement with no moving parts in the flow sensor. Service life depends on the model, water quality and operating conditions.

Calculation Method

Q = m × c × ∆t (Energy calculation based on flow rate and temperature difference)

Body Material

Brass, Cast Iron

Screen

Detachable from the body, easy-to-read 8-digit LCD display

Assembly

Can be connected horizontally or vertically

Energy Unit

Standard: kWh / Optional: MWh, Gcal, GJ

Measurement Performance
Measurement Performance
Temperature Range

5°C - 90°C

Minimum Temperature Difference (∆t)

3 K (UKM15–UKM100 type-examination scope)

Sensor Type

A pair of platinum temperature sensors capable of linear measurement

Magnetic Protection

It is not affected by magnetic fields

Pressure and Strength
Pressure and Strength
Pressure Class

PN16 (Max. Working Pressure: 16 bar, Test Pressure: 16 bar)

Minimum Operating Pressure

2 Bar

Protection Class

The catalogue specifies IP65 for the UKM series. Confirm the protection rating of the ordered model and its components against the technical datasheet and product label.

Communications and Energy
Communications and Energy
Standard Interface

M-Bus and optical interface

Optional Interface

Pulse, RF (Wireless M-Bus), LoRa/LoRaWAN

Compatibility

Compatible with ATLAS CNV or a LoRaWAN Gateway when the selected communication hardware and data format match. Verify interface and software compatibility for the project.

Power Supply

Low-energy-consumption lithium battery

Standards
Standards
Certification

MID 2014/32/EU MI004, TS EN 1434, 2004/22/EC

Accuracy Class

Class 2

Contents of the Pack
Contents of the Pack
Standard

Heat Meter, 2 Klingrit Gaskets, 1 Sensor Fitting and O-ring, Instruction Manual

Note

Union fittings are not included in the delivery.

Similar Products

ATLAS UKM20 DN20 ultrasonik ısı sayacı ve sıcaklık probu

ATLAS UKM20 DN20 Ultrasonic Heat Meter

ATLAS UKM25 DN25 ultrasonik ısı sayacı ve sıcaklık probu

ATLAS UKM25 DN25 Ultrasonic Heat Meter

ATLAS USM ultrasonik su sayacı – ürün görseli

Ultrasonic Water Meters

ATLAS mekanik tek hüzmeli su sayacı

Mechanical Single-Jet Water Meters

Dizüstü bilgisayar ekranında grafikler ve ölçüm verileri içeren web yönetim paneli

Heat / Bill Sharing Systems

Seres Solid mechanical heat meter with temperature sensors

Mechanical Heat Meters

ATLAS sıcaklık sensörü kovanlı küresel vana ürün görseli

Ball Valve with Sensor Pocket

ATLAS mekanik çok hüzmeli su sayacı

Mechanical Multi-Jet Water Meters

ATLAS pulse çıkışlı mekanik su sayacı ürün görseli

Single Jet Water Meters with Pulse Output

Dinamik balans ve fark basınç kontrol vanası ürün görseli

Dynamic Balancing / Differential Pressure Balancing Valve

ESTRON logolu analog manometre, yuvarlak basınç kadranı ve alt dişli bağlantı

Pressure Gauges

ESTRON EN 13190 thermometer

Thermometers

Boru hattı montaj ve demontaj parçası

Assembly / Disassembly Parts

Su sayacı bağlantı rekoru, sayaç tesisat bağlantı parçası

Brass Water Meter Coupling

ATLAS M-Bus Converter

M-Bus Converters

ATLAS EH-20

Electromechanical Water Meters

Termostatik başlıklı radyatör vanası — oda sıcaklığı kontrolü için vana ve termostatik başlık

Thermostatic Radiator Valves

Size Nasıl Yardımcı Olabiliriz?