Ultrasonic Heat Meters

ATLAS UKM ultrasonic heat meters measure energy consumption in heating and cooling systems, with M-Bus, pulse and LoRa/LoRaWAN communication options.
ATLAS UKM series ultrasonic heat meter

UKM series ultrasonic heat meters

ATLAS UKM ultrasonic heat meters measure energy in heating and cooling circuits. Select the body material, installation orientation and connection dimensions for the required model. M-Bus, pulse and LoRa/LoRaWAN communication options must match the ordered hardware and reading infrastructure. Models with the appropriate interface can connect to remote reading systems through ATLAS CNV or a LoRaWAN Gateway.

UKM series flow rates and connection dimensions

Type DN (mm) Connection Diameter Nominal Flow Rate (qp)[m³/h] Min. Flow Rate (qi)[m³/h] Max. Flow Rate (q)[m³/h] Length (L)[mm] Height (H)[mm] Width (W)[mm] Weight[gr]
UKM15 15 3/4″ Thread 1,50 0,03 / 0,012* 3,00 110 94 83 950
UKM20 20 1″ Thread 2,50 0,05 5,00 130 94 83 950
UKM25 25 11/4″ Thread 3,50 0,07 7,00 160 100 83 –
UKM32 32 11/2″ Thread 6,00 0,06 12,00 180 100 83 1100
UKM40 40 2″ Thread 10,00 0,10 20,00 200 120 83 1250
UKM50 50 Flanged 15,00 0,15 30,00 200 165 165 –
UKM65 65 Flanged 25,00 0,25 50,00 200 185 185 –
UKM80 80 Flanged 40,00 0,40 80,00 220 200 200 –
UKM100 100 Flanged 60,00 0,60 120,00 250 220 220 –
UKM125 125 Flanged 100,00 1,00 200,00 250 250 250 –
UKM150 150 Flanged 150,00 1,50 300,00 300 285 285 –
UKM200 200 Flanged 250,00 2,50 500,00 350 340 340 –
UKM250 250 Flanged 400,00 4,00 800,00 450 405 405 –
UKM300 300 Flanged 560,00 5,60 1120,00 500 460 460 –

Minimum flow rate and model documentation

This table is for preliminary selection. Confirm minimum flow rates (qi), including the starred 0.012 m³/h value for UKM15, against the current datasheet and type approval documentation of the ordered model. Some minimum flow values differ between the catalogue and web table; do not use them alone as definitive order specifications.

Selecting an ultrasonic heat meter

Pipe size alone is not enough to select a heat meter. Consider the minimum and nominal flow rates, installation length, connection type and communication requirements together.

  • Flow range: Compare each model’s minimum, nominal and maximum flow rates in the table above.
  • Installation: Match the DN, connection size and body length to the system design.
  • Operating conditions: Check temperature, pressure and protection ratings against the selected model’s technical documentation.

What is the difference between UKM15 and UKM20?

The table specifies a nominal flow rate of 1.50 m³/h and an installation length of 110 mm for UKM15, compared with 2.50 m³/h and 130 mm for UKM20. Select the model according to the system’s flow requirements and connection dimensions.

How do mechanical and ultrasonic heat meters compare?

Ultrasonic models measure flow using an ultrasonic principle without moving parts in the flow sensor. Mechanical heat meters use a mechanical flow sensor. Compare each model’s flow range, installation conditions and reading infrastructure.

Remote reading options

Assess M-Bus, pulse and LoRa/LoRaWAN options against your existing automation infrastructure. Explore M-Bus converters and the LoRaWAN Gateway. Confirm communication hardware and compatibility when ordering.

Request a project quotation

Provide the model or DN, design flow rate, installation length, quantity and preferred communication interface.

Request an ultrasonic heat meter quotation

General Structure and Design
General Structure and Design
Product Description

Ultrasonic heat meter used in heating and cooling systems

Principle of Measurement

Ultrasonic flow measurement with no moving parts in the flow sensor. Service life depends on the model, water quality and operating conditions.

Calculation Method

Q = m × c × ∆t (Energy calculation based on flow rate and temperature difference)

Body Material

Brass, Cast Iron

Screen

Detachable from the body, easy-to-read 8-digit LCD display

Assembly

Can be connected horizontally or vertically

Energy Unit

Standard: kWh / Optional: MWh, Gcal, GJ

Measurement Performance
Measurement Performance
Temperature Range

5°C - 90°C

Minimum Temperature Difference (∆t)

0,1°C

Sensor Type

A pair of platinum temperature sensors capable of linear measurement

Magnetic Protection

It is not affected by magnetic fields

Pressure and Strength
Pressure and Strength
Pressure Class

PN16 (Max. Working Pressure: 16 bar, Test Pressure: 16 bar)

Minimum Operating Pressure

2 Bar

Protection Class

The catalogue specifies IP65 for the UKM series. Confirm the protection rating of the ordered model and its components against the technical datasheet and product label.

Communications and Energy
Communications and Energy
Standard Interface

M-Bus and optical interface

Optional Interface

Pulse, RF (Wireless M-Bus), LoRa/LoRaWAN

Compatibility

Compatible with ATLAS CNV or a LoRaWAN Gateway when the selected communication hardware and data format match. Verify interface and software compatibility for the project.

Power Supply

Low-energy-consumption lithium battery

Standards
Standards
Certification

MID 2014/32/EU MI004, TS EN 1434, 2004/22/EC

Accuracy Class

Class 2

Contents of the Pack
Contents of the Pack
Standard

Heat Meter, 2 Klingrit Gaskets, 1 Sensor Fitting and O-ring, Instruction Manual

Note

Union fittings are not included in the delivery.