The ATLAS ADP dynamic balancing valve enables energy savings by regulating the water flow rate in heating and cooling systems. Dynamic balancing is achieved by controlling the water flow. In systems with variable flow and pressure values, the desired flow rates can be set using the ATLAS ADP dynamic balancing valve. By adjusting the required flow rate for each branch line, energy savings are achieved and the flow rate is tailored to meet specific needs. It eliminates flow-induced noise. It prevents excess flow and reduces system maintenance costs.
ADP selection and differential pressure
The 2026 catalogue configuration for DN20–DN50 is PN16, adjustment 5–25 kPa and maximum operating differential 150 kPa. Match these limits to the order code and drawing revision. Example: 35 kPa at the branch inlet minus 15 kPa across the controlled circuit and 8 kPa in other equipment leaves 12 kPa across the valve. Check it against the control curve; verify pressure tapping and impulse line routing.
| Model Name | DN (mm) | Kvs Value (m³/h) | PN (bar) | Max. Operating Differential Pressure (bar) | Adjustable Differential Pressure (kPa) | Length (mm) | Height (mm) |
|---|---|---|---|---|---|---|---|
| ADP 20 | 20 | 1,2 – 1,6 | 16 | 4,5 | 5 – 25 | 70 | 104 |
| ADP 25 | 25 | 1,2 – 8,6 | 16 | 4,5 | 5 – 25 | 120 | 160 |
| ADP 32 | 32 | 1,3 – 13 | 16 | 4,5 | 5 – 25 | 180 | 174 |
| ADP 40 | 40 | 1,2 – 1,6 | 16 | 4,5 | 5 – 25 | 200 | 220 |
| ADP 50 | 50 | 2,2 – 39 | 16 | 4,5 | 5 – 25 | 230 | 240 |
| ADP 65 | 65 | 2,2 – 58 | 16 | 4,5 | 20 – 80 | 290 | 300 |
| ADP 80 | 80 | 2,8 – 80 | 16 | 4,5 | 20 – 80 | 310 | 310 |
| ADP 100 | 100 | 2,2 – 58 | 16 | 4,5 | 20 – 80 | 350 | 375 |